Up to this point, we have explored several types of instrumentation diagrams, and in each one we have referred to different instruments by identifying them with letters such as TT (Temperature Transmitter), PDT (Pressure Differential Transmitter), or FV (Flow Valve), without formally defining the letters used to identify them.
Part of the ISA 5.1 Standard does exactly this, that is, define a nomenclature to identify instruments according to their functions and types; it is this part that we will focus on in this article.
Each instrument within a facility or plant must have its own unique identifier or TAG, consisting of a series of letters describing the instrument's function, as well as a number associated with its respective control loop. An optional prefix number can be included in the TAG to designate a specific area where the instrument is installed, and suffix letters to designate multiple instances of the instrument within the loop.
For example, if we see an instrument with the tag FC-135, we should know that it is a Flow Controller (FC) for control loop number 135. In large plants with multiple process units or areas, a tag might be preceded by another number that designates the area involved. For example, a flow controller might be labeled or tagged as 12-FC-135 (flow controller for loop #135, located in area or unit 12). If this loop has several controllers, we might need to distinguish one from another; in this case, we use letters at the end of the tag. (For example, 12-FC-135A, 12-FC-135B, 12-FC-135C).
All instruments within a particular loop are first defined by the variable that the loop senses or controls, regardless of their physical construction. In our hypothetical example, the FC-135 flow controller, for instance, could be physically identical to a loop level controller #72 (LC-72) or a loop temperature controller #288 (TC-288). What makes the FC-135 a flow controller is that the transmitter is sensing/controlling flow as the primary process variable. Similarly, the tag identification for every other instrument within the loop must also begin with the letter "F". It's important to note that in certain cases this rule is broken, for example, when we have a cascade or feedforward loop where multiple transmitter signals feed into the same controller. In this case, each transmitter is identified by the type of process variable it senses, and each controller is identified in the same way. This rule also includes the final control element: in a level control loop, the transmitter will be identified as an “LT” even if the sensed variable is indirectly measured by pressures (as in the case of a differential pressure transmitter), the controller will be identified as an “LC”, and the control valve acting on some flow will be identified as an “LV”, every instrument in that level control loop will help to control LEVEL and its primary function will be level control or measurement.
Several ISA-recognized nomenclatures for defining primary process instrument variables within a loop are shown in the following table. It's important to note that the use of a modifier defines a single variable; for example, "PT" is a pressure transmitter at a single point in a process. In contrast, "PDT" is a differential pressure transmitter between two points in a process. Similarly, "TC" is a temperature controller, while "TKC" is a rate-of-change-of-temperature controller.
| Letter | Variable | Modifier |
| A | Analytical (composition) | |
| B | Burner or Combustion | |
| C | User-defined | |
| D | User-defined | Differential |
| E | Voltage | |
| F | Flow | Ratio or Fraction |
| G | User-defined | |
| H | Hand (manual) | |
| I | Current | |
| J | Power | Sean |
| K | Time or Schedule | Time rate-of-change |
| L | Level | |
| M | User-defined | Momentary |
| N | User-defined | |
| 0 | User-defined | |
| P | Pressure or Vacuum | |
| Q | Quantity | Time-Integral or Total |
| R | Radiation | |
| S | Speed or Frequency | Safety |
| T | Temperature | |
| U | Multi-function | |
| V | Vibration | |
| w | Weight or Force | |
| X | Unclassified | X-axis |
| Y | Event, State, or Presence | Y-axis |
| Z | Position or Dimension | Z-axis |
A letter designated as “user-defined” represents a non-standard variable used multiple times in an instrumented system. For example, an engineer designing an instrumented system to measure and control the refractive index of a liquid might choose to use the letter “C” for this variable. Therefore, a refractive-index transmitter would be designated “CT” and a refractive-index control valve would be “CV”. This means that a user-defined variable needs to be defined in a specific location (e.g., in the legend of a diagram or drawing).
A letter designated as “unclassified” represents one or more non-standard variables, each used only once (or very few times) within the instrumented system.
To construct our tags, we must ensure they best represent the function involved in the process. For example, a "PT" is an instrument that transmits a signal representing pressure, while a PI is a pressure indicator and a "PC" is a pressure controller. Many instruments have multiple functions assigned by multiple letters, such as a TRC (Temperature Recording Controller). In other cases, the first letter represents a "passive" function (usually provided by the operator), while the second letter represents an "active" (automated) control function.
| Letter | Passive function | Active function | Modifier |
| A | Alarm | ||
| B | User-defined | User-defined | User-defined |
| C | Control | ||
| E | Element (sensing) | ||
| G | Glass or Viewport | ||
| H | High | ||
| I | Indicate | ||
| K | Control station | ||
| L | Light | Low | |
| M | Middle or Intermediate | ||
| N | User-defined | User-defined | User-defined |
| 0 | Goldsmith | ||
| P | Test point | ||
| R | Record | ||
| S | Switch | ||
| T | Transmit | ||
| U | Multi-function | Multi-function | Multi-function |
| V | Valve, Damper, Louver | ||
| W | Well | ||
| X | Unclassified | Unclassified | Unclassified |
| Y | Relay, Compute, Convert | ||
| Z | Driver, Actuator, or unclassified final control element |
A variety of letter combinations are frequently used to identify details not standardized by the ISA. For example, a chemical analyzer often has its sample inlet connection represented by the letter combination “SC”, even though this does not appear anywhere in the ISA 5.1 standard.
The following list shows some examples of commonly used tags:
- AIT = Analytical Indicating Transmitter (e.g., an oxygen concentration analyzer with a built-in display showing the percentage of concentration)
- ESL = Voltage Switch, Low (e.g., A switch used to detect low voltage conditions in an electrical power system)
- FFI = Flow Ratio Indicator (e.g., A device that tells us the air-fuel ratio for an industrial engine)
- FIC = Flow Indicating Controller (e.g., A controller designated to indicate flow to operators)
- HC = Hand Controller (Ej A device that allows the operator to set a desired level control signal, usually a valve)
- JQR = Power Totalizing Recorder (e.g., power recorder and tracking of energy used)
- LSHH = Level Switch, ie-ie. (e.g., Level switch to detect a high liquid level and initiate an automatic shutdown or interlock)
- LT = Level Transmitter (e.g., a level transmitter)
- PIT = Pressure Indicating Transmitter (e.g., a pressure transmitter that includes a display showing the pressure at the required engineering unit)
- PDT = Pressure Differential Transmitter (e.g., A pressure transmitter that can sense the pressure difference between two points in a process)
- PV = Pressure Valve (e.g., A control valve installed in a loop where the main variable is pressure)
- TEA = Temperature Element (e.g., a temperature sensor, such as a thermocouple, thermistor, bimetallic thermometer, etc.)
- TKAH = Temperature Rate-of-change Alarm, High (e.g., an alarm device that is activated when the rate of temperature change exceeds a set limit)
- TV = Temperature Valve (e.g., A control valve installed in a loop where the process variable is temperature).
- TY = Temperature Converter (e.g., an I/P transducer in a temperature loop)
- VSH = Vibration Switch, High (e.g., A switch used to detect high levels of vibration in a pump)
- ZXI, ZYI, and ZZI = Position Indicators for X, Y, and Z axes respectively (e.g., Indicators that show their positions on the three axes for a part of a CNC machine)
Do you want to learn more about instrumentation?
We are launching a PRE-SALE (at a special price) of our training course, "How to Learn Industrial Instrumentation Easily." If you would like to learn more about this training and have a chance to participate in our pre-launch, click below:
Go ahead, COMMENT and SHARE now!.
Help us grow
Finally, if you are determined to learn Industrial Automation and advance your professional career, you may be interested in our Premium courses:
– Click to see all our courses at MyAutomationClass.com
- Course: «"Become a PLC expert in 60 days, from basic to pro"»
- Course: «"PID Controllers Master Class – 100% practical"»
- Course: «"How to create SCADA/HMI projects from scratch with InTouch"»
- Course: «"PID Tuning Ultimate: The Definitive Course for Tuning"»
- Course: «"Practical Process Modeling: Definitive Steps to Becoming an Expert"»
- Program: «"The Ultimate Process Control Formula" (All-inclusive: PID Control, Tuning, and Modeling)
- Course: How to Learn Industrial Instrumentation, Easily (Complete)
If you have any questions, contact us via Facebook Messenger
Until next time. COMMENT AND SHARE! I'll be happy to answer your questions.



Very good contribution